Plan Review Notes
Plan Review Notes For Permit 18060522
Permit Number 18060522
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-28 06:17:541) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) FOUR SETS OF PLANS HAVE BEEN SUBMITTED BUT ONLY TWO
 SETS HAVE PUMP SPECS.CLARIFY.
 3) INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS
 APPLICABLE TO THE SPECIFIC PUMP BEING INSTALLED ON THIS
 SYSTEM. THIS IS REQUIRED TO MATCH THE CALCULATED TDH TO
 THE MAXIMUM SYSTEM FLOW RATE OF THE SYSTEM ON THE PUMP
 CURVE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  