| 2019-02-05 12:05:52 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 4TH REVIEW; DENIED |
| | |
| | COMMENTS NOTED BELOW ARE A RESTATEMENT OF PREVIOUS |
| | COMMENTS WHICH HAVE NOT BEEN ADDRESSED. |
| | 1. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE, |
| | HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB |
| | FPC 107.2.1. |
| | 2. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER |
| | RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH |
| | WPB FBC 107.2.1: |
| | A) COLD AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL |
| | VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL |
| | CHAPTER 6 |
| | B) THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER |
| | SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3 |
| | C) T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION |
| | IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5 |
| | AND 504.6 504.7, 504.7.1 AND 504.7.2. |
| | D) WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN |
| | ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2. |
| | |
| | PLEASE NOTE THAT SUBMITTED PLAN PAGE P0.1 IS REV 1 |
| | DATED 8/30/18 AND IT WAS NOTED ON THE LAST REVIEW THAT |
| | THERE WERE TWO (2) PLAN PAGES P0.1 ONE OF WHICH WAS REV |
| | 1 AND THE OTHER WHICH WAS REV 2. IT IS POSSIBLE THAT |
| | THE WRONG P0.1 WAS SUBMITTED AND THAT THE P0.1 REV 2 |
| | HAS THE REQUIRED INFORMATION. |
| | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, |
| | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING |
| | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |