| 2019-01-09 08:14:32 | 2017 FBC- PLUMBING PLAN REVIEW |
| | W. P. B. PERMIT: 18060517 |
| | ADD: 770 NORTHPOINT PKWY SUITE: 100 |
| | CONT: LEIGHTON MCGINN |
| | TEL: 561-308-2729 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: TUES. JAN. 08/2019 |
| | ACTION: DENIED |
| | |
| | 1A) 3RD REVIEW/ SEMI-COMPLIED. SHEET A2 DOES SHOW A |
| | NOTE THAT EXAM ROOM # 4 IS AN ACCESSIBLE EXAM ROOM. |
| | PLEASE NOTE THERE IS NO CLEAR FLOOR SPACE INDICATED ON |
| | THE FLOOR PLAN SHOWING COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTION606.2 CLEAR FLOOR SPACE. |
| | SHEET A3 DETAIL: 6 DOES INDICATE THIS IS THE ACCESSIBLE |
| | EXAM ROOM, BUT THE SINK IS SHOWN AT 36 INCHES ABOVE THE |
| | FINISH FLOOR, NOT IN COMPLIANCE WITH ACCESS. CODE |
| | SECTION 606.3 HEIGHT OF NO MORE THAN 34 INCHES ABOVE |
| | GRADE. THE PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH |
| | 606.4 FAUCET AND 606.5 EXPOSED PIPES AND SURFACES. |
| | |
| | 1B) NEW COMMENT. THERE ARE 2 P0.1 PLANS IN THE PLANS. |
| | ONE SHEET SHOW REVISION # 1 AND THE OTHER REVISION # 1 |
| | & 2. WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. |
| | |
| | 2A-D) COMPLIED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |