| 2019-01-08 11:57:07 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18060517 |
| | ADD: 770 NORTHPOINT PKWY SUITE: 100 |
| | CONT: LEIGHTON MCGINN |
| | TEL: 561-308-2729 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: TUES. JAN. 08/2019 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | |
| | NOTICE. 4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B). WITH RESPECT TO EVALUATION OF DESIGN |
| | PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS |
| | IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE |
| | FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | 4) 3RD REQUEST. THE PLANS SHEET A2 SHOWS THERE IS A LAB |
| | IN THIS TENANT SPACE. RESPONSE INDICATES WILL SUBMIT |
| | LATER UNDER A SEPARATE PERMIT. TO DO THIS YOU WILL NEED |
| | TO REMOVE THE LAB FROM THE SCOPE OF WORK. PLEASE BE |
| | AWARE UNDER THE BUILDING REVIEW AND MECHANICAL REVIEW |
| | THE REQUIREMENTS FOR A LAB WILL REQUIRE RATED WALLS |
| | VENTILATION REQUIREMENTS OTHER THAN A OFFICE (BUSINESS |
| | OCCUPANCY) AND THE REQUIREMENTS UNDER 307 HAZARDOUS |
| | MATERIAL, TABLE 307.1(1) MAXIMUM ALLOWABLE QUANTITIES |
| | OF MATERIALS PER CONTROL AREAS. CONTROL AREAS SEE 2017 |
| | FBC-B SECTION 414.2 CONTROL AREAS. CONTROL AREAS SHALL |
| | COMPLY WITH SECTIONS 414.2.1 THROUGH414.2.5 AND THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 5-6) COMPLIED. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |