| 2018-10-09 13:07:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK |
| | IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606 |
| | PER FBC ACC 212.3. THIS IS A SECOND REQUEST. PLEASE |
| | NOTE THAT THE ARCHITECT HAS NOT PROVIDED THIS |
| | INFORMATION ON THE PLANS AND NEEDS TO DO SO BEFORE THE |
| | PLUMBING PERMIT APPLICATION CAN BE APPROVED. THE |
| | PROVIDED INFORMATION BY THE ARCHITECT NEEDS TO INCLUDE |
| | SUCH THINGS AS THE DESIGNATED ACCESSIBLE ROOM (IE. EXAM |
| | RM #4), MILL WORK PLAN AND ELEVATION VIEWS, AND |
| | POSSIBLY ANOTHER DESIGNATED PLUMBING FIXTURE IN THE |
| | PLUMBING FIXTURE SCHEDULE. |
| | 2. RE: PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE, |
| | HLAV. SPECIFY IN THE FIXTURE DESCRIPTION AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. TO COMPLY WITH FBC PL 416.5 PER WPB |
| | FPC 107.2.1. THIS IS A SECOND REQUEST. |
| | 3. PROVIDE A DETAIL OF THE WATER HEATER AND HOT WATER |
| | RECIRC PUMP SHOWING THE FOLLOWING IN ACCORDANCE WITH |
| | WPB FBC 107.2.1: |
| | A. HOT AND COLD WATER PIPING ARRANGEMENT INCLUDING ALL |
| | VALVES IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL |
| | CHAPTER 6. |
| | B. THERMAL EXPANSION DEVICE REQUIRED ON COLD WATER |
| | SUPPLY TO WATER HEATER IN ACCORDANCE WITH FBC PL 607.3 |
| | C. T&P RELIEF VALVE AND DISCHARGE INCLUDING TERMINATION |
| | IN ACCORDANCE WITH FBC PL 504.1, 504.4, 504.4.1, 504.5 |
| | AND 504.6 504.7, 504.7.1 AND 504.7.2. |
| | D. WATER HEATER PAN AND DRAIN INCLUDING TERMINATION IN |
| | ACCORDANCE WITH FBC PL 504.7, 504.7.1 AND 504.7.2. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |