| 2018-08-07 07:18:59 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK |
| | IN EACH TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC |
| | 606. PER FBC ACC 212.3 |
| | |
| | 2. SHT. P0.1 THE SANITARY ISOMETRIC IS MISSING THE |
| | FOLLOWING PLUMBING FIXTURES, ALL THE SINKS IN THE SONO |
| | ROOMS, THE LAVATORY AND URINAL IN THE MENS BATHROOM |
| | PLEASE CLARIFY, PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. P0.1 BOTH THE SANITARY AND WATER ISOMETRIC |
| | DRAWING ARE TO COMPACT AND CONGESTED TO DETERMINE CODE |
| | COMPLIANCE PLEASE EXPAND THE SANITARY AND WATER |
| | ISOMETRIC DRAWINGS, PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT. P0.1 THE SANITARY ISOMETRIC THE SINK IN EXAM |
| | ROOM #4 AND LAB SHALL CONNECT TO THE BUILDING DRAIN |
| | SEPARATELY THE THE BATHROOM GROUP. PER FBC PL 912.1 |
| | |
| | 5. ALL LAVATORY'S USED BY THE PUBLIC SHALL HAVE ONLY |
| | TEMPERED WATER AND SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 6. SHT. P0.1 THE WATER ISOMETRIC IS MISSING THE |
| | FOLLOWING PLUMBING FIXTURES, THE MEN AND WOMENS |
| | BATHROOMS M PLEASE CLARIFY, PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |