| 2018-06-25 17:55:45 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18060517 |
| | 6/25/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL NEW |
| | ROOMS AND SPACES- SECTION 809.2 FBC EX, AND TABLE |
| | 403.3.1.1 FBC M. |
| | |
| | 2) THE PLANS SHOW A LAB ROOM. REFER TO SECTION 510.1 |
| | FBC M AND CLARIFY WHAT PROCESSES ARE TO TAKE PLACE IN |
| | THE ROOM, AND WHAT CHEMICALS, IF ANY, ARE STORED IN THE |
| | ROOM AND THEIR QUANTITIES. |
| | |
| | 3) THERE ARE TWO EXISTING AC TRUNK LINES ON THE EAST |
| | AND WEST SIDE OF THE SPACE THAT DO NOT SHOW ANY |
| | CONTINUATIONS TO AIR HANDLER UNITS. PLEASE PROVIDE |
| | NOTES TO CLARIFY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |