| Plan Review Notes For Permit 18060510 |
| Permit Number |
18060510 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-14 13:00:58 | PLAN DENIED | | | 1) PROVIDE CFM ON ALL SUPPLY GRILES PER SECTION 107 | | | 2017 FBC | | | 2) PROVIDE SIZE OF RETURN AIR GRILL ABOVE DOOR SECTION | | | 107 FBC 2017 | | | 3) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DETA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE | | | FOR THE DESIGN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|