| Plan Review Notes For Permit 18060457 |
| Permit Number |
18060457 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-08-24 16:03:36 | MECHANICAL PROVISOS: | | | CCOLE- 8/24/18 | | | | | | 1) THE KITCHEN HOOD MAKEUP AIR FAN (KSF) SHALL BE IN | | | COMPLIANCE WITH SECTION 506.5.1.2 FBC M. | | | | | | 506.5.1.2 IN-LINE FAN LOCATION. | | | | | | WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE | | | FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN | | | A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING | | | AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR | | | SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR | | | SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN | | | MANUFACTURER?S INSTALLATION INSTRUCTIONS.\ | | | | | | 2) COMPLIANCE WITH SECTION 508.1.1 FBC M REQUIRED. | | | | | | 508.1.1 MAKEUP AIR TEMPERATURE. | | | | | | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE | | | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F | | | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS | | | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE | | | HVAC SYSTEM. | | | | | | | | | | | | | | | |
|