2018-08-24 16:03:36MECHANICAL PROVISOS:
 CCOLE- 8/24/18
  
 1) THE KITCHEN HOOD MAKEUP AIR FAN (KSF) SHALL BE IN
 COMPLIANCE WITH SECTION 506.5.1.2 FBC M.
  
 506.5.1.2 IN-LINE FAN LOCATION.
  
 WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE
 FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN
 A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING
 AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR
 SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR
 SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.\
  
 2) COMPLIANCE WITH SECTION 508.1.1 FBC M REQUIRED.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
  
  
  