| 2018-08-02 12:04:12 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #18060457 |
| | MASTER #18020254 |
| | 8/2/18 |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED STRUCTURAL ENGINEERING FOR TIE DOWN OF |
| | THE VRF CONDENSERS IS NOT ELECTRONICALLY SIGNED AND |
| | SEALED BY THE ENGINEER WHO PREPARED THE DRAWING- |
| | SECTION 61G15-23.005 FAC. A) THE DRAWING DOES NOT |
| | SPECIFICALLY REFERENCE WHICH ROOFTOP UNITS ARE TO BE |
| | INSTALLED IN ACCORDANCE WITH THE ENGINEERING. B) THE |
| | DRAWING DOES NOT INDICATE LATERAL AND UPLIFT PRESSURES |
| | BASED ON THE DESIGN CRITERIA AND THE DIMENSIONS OF THE |
| | UNITS. C) THE DESIGN INDICATES THE UNITS NEED TO BE |
| | STRAPPED TO THE SUPPORT BEAMS WHICH DOES NOT APPEAR TO |
| | BE COMPATIBLE WITH THE DESIGN OF THE VRF CONDENSERS, |
| | AND WILL ALSO REQUIRE REMOVAL OF STRAPPING FOR |
| | SERVICING. PLEASE NOTE THAT COMPLETE WIND LOAD |
| | ENGINEERING FOR ALL THE ROOFTOP UNITS IS REQUIRED |
| | INCLUDING THE OAU-1 & 2, THE VRF CONDENSERS, AND THE |
| | SMOKE CONTROL FANS AND FAN CURBS. |
| | |
| | 2) THE SUBMITTED NARRATIVE RESPONSE INDICATES |
| | ADJUSTMENT OF VALUE BASED ON THE ELECTRICAL ONLY. |
| | PLEASE INCLUDE THE VALUE INCREASE FOR MECHANICAL WHICH |
| | INCLUDES THE CHANGE TO THE VRF SYSTEMS. |
| | |
| | 3) PLEASE INDICATE ON THE PLANS THAT ALL FIRE/SMOKE |
| | DAMPERS AT SHAFT LOCATIONS WILL BE MOTORIZED TO OPERATE |
| | AUTOMATICALLY IN SEQUENCE WITH THE SMOKE CONTROL |
| | SYSTEM. PROVIDE AN "M" SYMBOL AT EACH LOCATION. |
| | |
| | 4) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR |
| | THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING |
| | APPROVAL BY THE ENGINEER OF RECORD. PLEASE NOTE THAT |
| | WIND LOAD ENGINEERING FOR THE ROOFTOP UNITS MAY BE |
| | ADDED TO THE LIST IF REQUESTED. |
| | |
| | A) SMOKE CONTROL FANS. |
| | B) FIRE AND FIRE/SMOKE DAMPERS. |
| | C) BAROMETRIC DAMPERS |
| | D) DUCT SMOKE DETECTORS |
| | E) AC ROOF AND DUCT STANDS, WALL BRACKETS |
| | F) EXHAUST AND OUTSIDE AIR LOUVERS |
| | G) PIPING INSULATIONS |
| | H) ACCESS PANELS |
| | I) GENERATOR |
| | J) COMMERCIAL CLOTHES DRYERS |
| | K) COOKING APPLIANCES |
| | L) DUCT FIRE WRAPPING |
| | M) FIRESTOPPING AND FIRE CAULKING |
| | |
| | 5) PLEASE SEE THE PROVISO NOTES UNDER THE MASTER PERMIT |
| | #18020254. IT IS IMPORTANT THAT THESE REQUIREMENTS ARE |
| | MET AS SOON AS POSSIBLE TO AVOID CONFLICTS IN THE |
| | FIELD, AND TO AVOID DELAYS IN CONSTRUCTION, AND FOR CO |
| | OF THE BUILDING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |