| Plan Review Notes For Permit 18060457 |
| Permit Number |
18060457 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-26 18:38:14 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON REVISION APPLICATION | | | APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE | | | AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. | | | FBC 109.3 | | | 2. PLAN SHOWING NEW UNITS IS CALLING OUT CIRCUITS FROM | | | PANELS THAT DON'T EXIST ON THE RISER DIAGRAM OR IN THE | | | PANEL SCHEDULES. PROVIDE CORRECTIONS. NEC 215.2, 215.5, | | | 408.4, 408.30; WPB FBC 107.2.1 | | | 3. PROVIDE CORRECTED LOAD CALCULATIONS WITH NEW PANEL | | | SCHEDULES. NEC 220 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|