Plan Review Notes
Plan Review Notes For Permit 18060454
Permit Number 18060454
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-12 17:33:0106/12/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PERMIT APPLICATION IS NOT SIGNED. FBC 105.3
  
 2) VALUE SEEMS LOW. PROVIDE BONA FIDE SIGNED CONTRACT.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 3) SHOW PIPING MATERIAL , SIZING OF PIPE, AND LIST
 SLEEVES. SHOW CONNECTION POINT TO WHERE THE SUPPLY
 PIPING WILL CONNECT TO THE REQUIRED BACKFLOW. FBC
 107.3.5
  
 4) PLANS ARE NOT SIGNED AND SEALED AS REQUIRED IN FL
 ADMIN CODE 61G1-23.001
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  