| Plan Review Notes For Permit 18060448 |
| Permit Number |
18060448 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-03 16:26:28 | 1ST REVIEW FBC-2014 MECHANICAL | | | REVISION #18060448 | | | MASTER PERMIT #17051281 | | | 7/3/18 | | | | | | CODES IN EFFECT: | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE 3M DUCT WRAP APPLIED TO THE DRYER EXHAUST DUCT | | | IS NOT AN ACCEPTABLE MEANS TO ALLOW THE DUCT TO RUN | | | THROUGH THE RETURN PLENUM ABOVE THE CEILING. THE | | | MANUFACTURER'S SPECIFICATIONS DO NOT PROVIDE AN | | | INSTALLATION METHOD FOR WRAPPING DRYER EXHAUST DUCTS, | | | AND THE INSTALLATION INSTRUCTIONS PROVIDED BY THE | | | MANUFACTURER ALSO REQUIRE DRYWALL SCREWS TO ATTACH THE | | | WRAP TO GREASE OR VENTILATION DUCTS. PLEASE NOTE THAT | | | SCREW PENETRATIONS INTO THE EXHAUST DUCT ARE PROHIBITED | | | PER SECTION 504.4, AND SCREWS FOR JOINING THE DUCT ARE | | | LIMITED TO PNETRATIONS OF 1/8". PLEASE PROVIDE A PLENUM | | | RATED ENCLOSURE USING NON COMBUSTIBLE OR PLENUM RATED | | | MATERIALS SUCH AS STEEL STUDS AND DRYWALL- SECTION | | | 602.2.. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|