2018-06-13 11:01:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO HAVE ADDRESS OF PROJECT. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 2. PLAN IS REQUIRED TO BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. ONLY THE
 SIGNATURE IS PRESENT. PROVIDE PRINTED NAME ALSO. WPB
 FBC 107.2.1
 3. THERE ARE SEVERAL CHANGES TO THIS PLAN FROM THE
 ORIGINAL THAT ARE NOT CLOUDED ON PLAN. PLAN SHOULD
 INDICATE ALL REVISIONS. WPB FBC 107.2.1
 4. PLAN STATES THAT PANEL WILL BE TURNED IN TO THE
 LAUNDRY ROOM, BUT THE ROOM IN QUESTION IS THE STORAGE
 ROOM? IT APPEARS THAT THE PANEL WILL NOT HAVE THE
 CLEARANCE REQUIRED PER NEC 110.26. PROVIDE CORRECTION.
 5. LUTRON PANELS ARE SHOWN APPROXIMATELY 2 FEET FROM
 WATER HEATER. PROVIDE CORRECTION FOR REQUIRED CLEARANCE
 PER NEC 110.26
 6. PROVIDE ACCURATE LOAD CALCULATION. BOTH AIR
 CONDITIONERS ARE CALCULATED AT 4000 VA, BUT MECHANICAL
 PLAN SHOWS ONE AS 4014 VA, AND THE OTHER AS 7176 VA.
 TOTAL VA IS DIVIDED BY 240, BUT THIS IS A SINGLE PHASE
 208 VOLT PANEL, SO 208 SHOULD BE USED FOR CALCULATION.
 NEC 220, 110.4, 300.2
 7. BASED ON AN ACCURATE LOAD CALCULATION USING THE
 PROPER VOLTAGE, IT APPEARS THE PANEL AND FEEDERS WILL
 BE OVERLOADED. PROVIDE CORRECTION. NEC 310.15, 408.30,
 408.36
 8. PLAN SHOWS A RECEPTACLE FOR A TV IN THE SPA TUB
 AREA. THIS RECEPTACLE OUTLET IS NOT PERMITTED PER CODE.
 PROVIDE CORRECTION. NEC 406.9(C)
 9. THERE IS A SUBSTANTIAL AMOUNT OF WORK INCLUDED IN
 THIS REVISION, HOWEVER, THE REVISION APPLICATION STATES
 THAT THERE IS NO INCREASE IN VALUE OF WORK. PROVIDE
 COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK,
 TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 10. ALL RECEPTACLES LOCATED IN BATHROOMS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 11. ALL KITCHEN COUNTER TOP RECEPTACLES REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 12. BREAKER FOR SPA TUB REQUIRES GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 680.43(A)(3)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  