| Plan Review Notes For Permit 18060396 |
| Permit Number |
18060396 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-27 09:10:12 | 1) CITY RECORDS SHOW A GAS GRILL ALSO CONNECTED TO THIS | | | LINE. SHOW THE GAS GRILL ON THE PLAN AND SHOW THE BTU | | | LOAD OF THE GRILL. THE BTU LOAD OF THE GAS GRILL SHALL | | | BE INCLUDED IN THE TOTAL BTU LOAD ON THIS LINE. | | | 2) THE LONGEST RUN SHOWN ON THE EXISTING GAS DRAWING IS | | | 60 FEET TO THE GAS GRILL. THIS DISTANCE SHALL BE USED | | | IN THE SIZING OF THIS GAS SYSTEM. 2017 FBC-FUEL GAS | | | SEC. 402.4.1. | | | 3) USING THE 60 FEET DISTANCE COLUMN, THE 1/2 INCH | | | GALVANIZED LINE TO THE GENERATOR IS UNDERSIZED PER GAS | | | SIZING TABLE 402.4 (4). THE MINIMUM SIZE SHALL BE 3/4 | | | INCH. | | | 4) THE 1 INCH PE LINE IS UNDERSIZED FOR A 60 FEET | | | DISTANCE AND BTU LOAD PER TABLE 402.4 (21) OF THE 2017 | | | FBC-FUEL GAS. | | | | | | NOTE: I HAVE A PLACED A COPY OF THE GAS DRAWING FROM | | | CITY RECORDS IN THE PERMIT APPLICATION FILE FOR YOUR | | | REVIEW AND REFERENCE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|