Plan Review Notes
Plan Review Notes For Permit 18060396
Permit Number 18060396
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-20 12:16:541) CITY RECORDS SHOW PREVIOUS GAS PERMITS SHOWING AN
 EXISTING GAS STOVE,DRYER AND GAS GRILL WITH A TOTAL
 DEVELOPED LENGTH OF 60 FT. TO THE MOST REMOTE FIXTURE.
 THIS DISTANCE SHALL BE USED IN THE SIZING OF THIS
 SYSTEM.2017 FBC-FUEL GAS SEC.401.3.
 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 3) SUBMIT A LEGIBLE GAS DRAWING WITH LEGIBLE NOTES ON
 IT.
 4) THE GAS SIZING TABLES THAT HAVE BEEN SUBMITTED ARE
 NOT FROM THE 2017 FBC-FUEL GAS CODE. SUBMIT COPIES FROM
 THE CURRENT CODE AND THIS INFO SHALL BE ON THE TABLES.
 WPB AMEND. FBC SEC. 107.2.1.
 5) THE SIZING TABLES SUBMITTED ARE PARTIALLY ILLEGIBLE
 DUE TO BEING ENLARGED. SUBMIT TWO COPIES OF LEGIBLE
 TABLES. WPB AMEND. TO FBC SEC. 107.2.1.
 6) THERE IS AN 8 1/2 X 11 COPY OF A SURVEY WITH NOTES
 THAT ARE ILLEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES
 FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1.
 7) THE LOCATION OF THE GENERATOR SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION MANUAL. 2017 FBC-FUEL GAS
 SEC.616.1.
 8) THE INSTALLATION OF THE GENERATOR SHALL COMPLY WITH
 NFPA 37.
 NFPA 37
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  