| 2018-06-20 12:16:54 | 1) CITY RECORDS SHOW PREVIOUS GAS PERMITS SHOWING AN |
| | EXISTING GAS STOVE,DRYER AND GAS GRILL WITH A TOTAL |
| | DEVELOPED LENGTH OF 60 FT. TO THE MOST REMOTE FIXTURE. |
| | THIS DISTANCE SHALL BE USED IN THE SIZING OF THIS |
| | SYSTEM.2017 FBC-FUEL GAS SEC.401.3. |
| | 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | 3) SUBMIT A LEGIBLE GAS DRAWING WITH LEGIBLE NOTES ON |
| | IT. |
| | 4) THE GAS SIZING TABLES THAT HAVE BEEN SUBMITTED ARE |
| | NOT FROM THE 2017 FBC-FUEL GAS CODE. SUBMIT COPIES FROM |
| | THE CURRENT CODE AND THIS INFO SHALL BE ON THE TABLES. |
| | WPB AMEND. FBC SEC. 107.2.1. |
| | 5) THE SIZING TABLES SUBMITTED ARE PARTIALLY ILLEGIBLE |
| | DUE TO BEING ENLARGED. SUBMIT TWO COPIES OF LEGIBLE |
| | TABLES. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) THERE IS AN 8 1/2 X 11 COPY OF A SURVEY WITH NOTES |
| | THAT ARE ILLEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES |
| | FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) THE LOCATION OF THE GENERATOR SHALL COMPLY WITH THE |
| | MANUFACTURER'S INSTALLATION MANUAL. 2017 FBC-FUEL GAS |
| | SEC.616.1. |
| | 8) THE INSTALLATION OF THE GENERATOR SHALL COMPLY WITH |
| | NFPA 37. |
| | NFPA 37 |
| | 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR |
| | WEATHERPROOF |
| | HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS |
| | SHALL |
| | BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS |
| | AND AT |
| | LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE |
| | WALLS. A |
| | MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER |
| | OF THE |
| | FOLLOWING CONDITIONS EXIST: |
| | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5 |
| | M (5 FT) |
| | FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING |
| | OF |
| | AT LEAST 1 HOUR. |
| | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE |
| | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE |
| | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS |
| | OUTSIDE THE ENCLOSURE. |
| | |