| Plan Review Notes For Permit 18060375 |
| Permit Number |
18060375 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-20 07:32:08 | 1) SUBMIT TWO CCOPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE MP REGULATOR BEING USED. | | | IDENTIFY ON THE SPECS WHICH MODEL IS BEONG USED & THE | | | ORIFICE SIZE TO ENSURE THE REGULATOR CAN ACCOMMODATE | | | THE ANTICIPATED BTU LOAD. REGULATORS INSTALLED OUTDOORS | | | SHALL BE RATED FOR EXTERIOR USE. 2017 FBC-FUEL GAS | | | SEC.410.1. | | | 2) THE PLANS REFERENCE NFPA 15. THIS STANDARD IS FOR | | | WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION AND HAS | | | NOTHING TO DO WITH NATURAL GAS. CLARIFY. | | | 3) THE GENERATOR DISTANCE FROM BUILDING OPENINGS SHALL | | | COMPLY WITH THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS. THIS IS USUALLY 10 FEET. | | | 4) DESCRIPTION OF WORK SHALL BE COMPLETED ON THE GAS | | | PERMIT APPLICATION.WPB AMEND. TO FBC SEC. 107.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|