Notes
Date Text
2018-06-15 14:35:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED DOES NOT SHOW WHAT THE MANUAL
 TRANSFER SWITCH IS FEEDING. IT APPEARS THAT THE
 TRANSFER SWITCH IS BACK FEEDING THE MAIN PANEL, WHICH
 IS NOT PERMITTED PER CODE. WILL THERE BE A SUB-PANEL
 INSTALLED AND CIRCUITS FOR GENERATOR RELOCATED TO THIS
 PANEL? PROVIDE CLARIFICATION. WPB FBC 107.2.1; NEC
 702.5
 2. LOAD CALCULATION PROVIDED IS NOT A LOAD CALCULATION
 PER CODE. PROVIDE ACCURATE LOAD CALCULATION FOR ITEMS
 THAT WILL BE ON GENERATOR WITH A DESCRIPTION OF THE
 CIRCUITS INVOLVED AND HOW THEY WILL BE FED FROM
 GENERATOR. SEE FBC RESIDENTIAL E3602.2 FOR AN EXAMPLE
 OF WHAT THE LOAD CALCULATION SHOULD INCLUDE. NEC 220,
 702.4(B); FBC RE E3602.2
 3. WHAT IS THE RATING OF THE MANUAL TRANSFER SWITCH?
 PROVIDE SPEC SHEET. NEC 110.3; WPB FBC 107.2.1
 4. EACH PAGE OF ELECTRICAL PLAN IS REQUIRED TO BE
 SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. PROVIDE
 CORRECTION. FS 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 5. PERMIT APPLICATION STATES THIS IS A PORTABLE
 GENERATOR. PROVIDE DETAIL OF HOW THE WIRING FROM THE
 PORTABLE GENERATOR WILL BE CONNECTED TO THE 60 AMP
 DISCONNECT SHOWN. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  