2018-07-10 07:39:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 1) COMMENTS FROM FIRST REVIEW HAVE NOT BEEN ADDRESSED.
 NO PLANS FOR THE GENERATOR PAD WERE SUBMITTED WITH THE
 REQUESTED INFORMATION. SEE COMMENTS BELOW.
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE TWO SETS OF A GENERATOR PAD DETAIL PLAN.
 SPECIFY THE METHOD OF CRACK CONTROL THAT WILL BE USED (
 FIBERMESH CONCRETE OR 6X6 W1.4X1.4 WELDED WIRE MESH).
 FBC-R506.2.4.2
  
 2) SPECIFY THE TYPE, LOCATIONS AND NUMBER OF ANCHORS
 AND THE REQUIRED EMBED DEPTHS OF THE ANCHORS ON THE
 DRAWINGS. FBC 107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  