| Plan Review Notes For Permit 18060362 |
| Permit Number |
18060362 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-10 07:39:08 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | 1) COMMENTS FROM FIRST REVIEW HAVE NOT BEEN ADDRESSED. | | | NO PLANS FOR THE GENERATOR PAD WERE SUBMITTED WITH THE | | | REQUESTED INFORMATION. SEE COMMENTS BELOW. | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE TWO SETS OF A GENERATOR PAD DETAIL PLAN. | | | SPECIFY THE METHOD OF CRACK CONTROL THAT WILL BE USED ( | | | FIBERMESH CONCRETE OR 6X6 W1.4X1.4 WELDED WIRE MESH). | | | FBC-R506.2.4.2 | | | | | | 2) SPECIFY THE TYPE, LOCATIONS AND NUMBER OF ANCHORS | | | AND THE REQUIRED EMBED DEPTHS OF THE ANCHORS ON THE | | | DRAWINGS. FBC 107.2.1 | | | | | | 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 4) N/A |
|