| Plan Review Notes For Permit 18060362 |
| Permit Number |
18060362 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-14 15:40:36 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | | LOADS.THAT WILL BE ON THE GENERATOR NEC 220; FBC RE E | | | E3602.2 | | | | | | PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY PERSON | | | RESPONSIBLE FOR THE DESIGN. FS 481.229; FBC.3.5 | | | | | | PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; | | | FBC 107.2.1 |
|