Plan Review Notes
Plan Review Notes For Permit 18060362
Permit Number 18060362
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-28 16:45:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A GENERATOR PAD DETAIL PLAN. SPECIFY THE
 METHOD OF CRACK CONTROL THAT WILL BE USED ( FIBERMESH
 CONCRETE OR 6X6 W1.4X1.4 WELDED WIRE MESH).
 FBC-R506.2.4.2
  
 2) SPECIFY THE TYPE, LOCATIONS AND NUMBER OF ANCHORS
 AND THE REQUIRED EMBED DEPTHS OF THE ANCHORS ON THE
 DRAWINGS. FBC 107.2.1
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) PROVIDE THE GENERATOR MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS THAT SHOW THE REQUIRED
 GENERATOR PAD DIMENSIONS. FBC 107.2.1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved