2018-07-11 11:53:371ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 REVISION #18060327
 MASTER #17100298
 7/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PLEASE REMOVE THE PAD MOUNTED CONDENSER
 DETAIL AND REPLACE IT WITH A WALL MOUNTED CONDENSER
 BACKET DETAIL WITH COMPLETE ANCHORING AND FASTENING
 DETAILS. SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE BRACKET WITH APPROVAL STAMP BY THE DESIGN
 PROFESSIONAL OF RECORD.
  
 2) M-1: THE PLAN INDICATES FLEX EXHAUST DUCTS ARE TO BE
 INSTALLED FOR THE BATH AND KITCHEN EXHAUST SYSTEMS.
 PLEASE INDICATE THE TYPE OF FLEX DUCTS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN EXHAUST
 HOOD AND EXHAUST DUCT.
  
 3) SUBMIT A REVISED 2ND FLOOR AC PLAN (APPLICABLE ONLY
 IF CHANGES WERE MADE).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  