| Plan Review Notes For Permit 18060327 |
| Permit Number |
18060327 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-11 11:53:37 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | REVISION #18060327 | | | MASTER #17100298 | | | 7/11/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: PLEASE REMOVE THE PAD MOUNTED CONDENSER | | | DETAIL AND REPLACE IT WITH A WALL MOUNTED CONDENSER | | | BACKET DETAIL WITH COMPLETE ANCHORING AND FASTENING | | | DETAILS. SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE | | | NOA FOR THE BRACKET WITH APPROVAL STAMP BY THE DESIGN | | | PROFESSIONAL OF RECORD. | | | | | | 2) M-1: THE PLAN INDICATES FLEX EXHAUST DUCTS ARE TO BE | | | INSTALLED FOR THE BATH AND KITCHEN EXHAUST SYSTEMS. | | | PLEASE INDICATE THE TYPE OF FLEX DUCTS AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN EXHAUST | | | HOOD AND EXHAUST DUCT. | | | | | | 3) SUBMIT A REVISED 2ND FLOOR AC PLAN (APPLICABLE ONLY | | | IF CHANGES WERE MADE). | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|