| Date |
Text |
| 2018-07-11 18:06:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18060308 |
| | 7/11/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-121: PROVIDE A MEANS OF RETURNING AIR FROM |
| | THE BEDROOMS- SECTION 601.6 FBC M. |
| | |
| | 2) M-121: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | NEW COOKING APPLIANCE- SECTION 917.1 FBC M. |
| | |
| | 3) M-121: EXHAUST VENTILATION IS REQUIRED FOR THE |
| | KITCHEN AT A RATE OF 25 CFMS CONTINUOUS, OR 100 CFMS |
| | INTERMITTENTLY PER TABLE 403.3.1.1 FBC M. INDICATE IF A |
| | NEW KITCHEN EXHAUST HOOD AND EXHAUST DUCT ARE TO BE |
| | INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE SYSTEM. B) PROVIDE A DETAIL SHOWING THE EXHAUST |
| | DUCT RUN AND TERMINATION LOCATION- SECTION 505 FBC M |
| | |
| | 4) CLARIFY IF A NEW OR RELOCATED DRYER IS TO BE |
| | INSTALLED AND: A) SUBMIT MANUFACTURER'S SPECIFICATIONS. |
| | B) SHOW THE LOCATION OF THE DRYER AND THE EXHAUST DUCT |
| | RUN AND TERMINATION LOCATION.- SECTION 504 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |