| Date |
Text |
| 2018-06-27 09:25:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE SUBMITTED PLAN INDICATES ONE ADDRESS - 315 S |
| | FLAGLER DR., HOWEVER, THEY INDICATE WORK ON FLOORS 10 - |
| | 11 & 12, WHICH APPEARS TO BE INDIVIDUAL UNITS. |
| | |
| | THERE IS NO INDICATIONS OF INTERNAL STAIRS CONNECTING |
| | THE FLOORS. |
| | |
| | THESE INDIVIDUAL UNITS ARE NOT INDICATED WITH THEIR |
| | CORRESPONDING NUMBERS. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY IN ADDITION TO # 2 |
| | BELOW |
| | |
| | |
| | |
| | 2) EACH OF THESE INDIVIDUAL UNITS WITH THE PROPOSED |
| | WORK SHOULD BE SUBMITTED UNDER INDIVIDUAL PERMITS WITH |
| | THE CORRESPONDING UNIT NUMBERS AS NOTED IN # 1 ABOVE. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) A FIRE SPRINKLER SHEET WAS PROVIDED; HOWEVER, THERE |
| | IS NO INDICATION THAT THE WORK SHALL BE DONE UNDER |
| | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED AND |
| | OPERATIONAL DURING ALL CONSTRUCTION PERIODS. |
| | |
| | IF THE SYSTEM IS DOWN FOR MORE THAN 4 HOURS, YOU ARE |
| | REQUIRED TO NOTIFY THE AHJ AND CONDUCT A FIRE WATCH. |
| | |
| | PLEASE REVIEW AND CORRECT FOR EACH INDIVIDUAL UNIT. |
| | |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF WORK ON THE FIRE ALARM |
| | SYSTEM AND THAT ANY WORK ON THE FIRE ALARM SYSTEM SHALL |
| | BE DONE UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | |
| | THE FIRE ALARM SYSTEM SHALL BE MAINTAINED AND |
| | OPERATIONAL DURING ALL CONSTRUCTION PERIODS. |
| | |
| | IF THE SYSTEM IS DOWN FOR MORE THAN 4 HOURS, YOU ARE |
| | REQUIRED TO NOTIFY THE AHJ AND CONDUCT A FIRE WATCH. |
| | |
| | PLEASE REVIEW AND CORRECT FOR EACH INDIVIDUAL UNIT. |
| | |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |