| 2018-07-23 11:00:48 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE G2 ON SHEET E-001 AND SHEET G-100 SPECIFY THE |
| | WRONG CODE FOR DESIGN. THESE ARE IN CONFLICT WITH OTHER |
| | AREAS OF THE PLAN THAT STATE THE CURRENT CODE. CORRECT |
| | DISCREPANCIES. WPB FBC 107.2.1; FBC PREFACE |
| | 2. DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE |
| | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| | 3. BE ADVISED THAT FIRE ALARM IS NOT INCLUDED IN THE |
| | SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1 |
| | 4. SHEET E-002 HAS A NOTE FOR PATIENT CARE AREAS, BUT |
| | REVIEWER DOES NOT SEE ANY PATIENT CARE AREAS IDENTIFIED |
| | ON PLAN. PROVIDE CLARIFICATION AND/OR CORRECTION. WPB |
| | FBC 107.2.1 |
| | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL TO CONFIRM THE STATED AIC RATING OF THE PANELS IS |
| | ADEQUATE. NEC 110.9, 110.10 |
| | 6. NOTE ON PANEL SCHEDULE INDICATES THAT ALL BREAKERS |
| | SHALL BE AFCI TYPE. BRANCH CIRCUITS THAT FEED EQUIPMENT |
| | SUCH AS A RANGE OR AN AC ARE NOT TYPICALLY INSTALLED |
| | WITH AFCI PROTECTION. PROVIDE CLARIFICATION AS TO WHICH |
| | CIRCUITS ARE AFCI PROTECTED PER CODE. NEC 210.12 |
| | 7. PLAN SHOWS WHAT APPEARS TO BE A STANDARD RECESS |
| | LIGHT OVER SHOWER. LIGHTING IN BATHTUB OR SHOWER AREAS |
| | SHALL BE SUITABLE FOR DAMP LOCATIONS. PROVIDE |
| | CORRECTION. NEC 410.10(D) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |