2018-06-30 12:08:221ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE REVISED SHTS. PF.1.1.1, PF.2.1.1,
 PF.3.1.1, PF.3.2.1. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE REVISED GREASE INTERCEPTOR SIZING
 CALCULATIONS FROM SCHIER MANUFACTURING. PER WPB AMEND
 TO FBC 107.2.1
  
 3. SHOW TWO WAY CLEAN OUTS BETWEEN ALL GREASE
 INTERCEPTORS. PER MANUFACTURE INSTALLATION GUIDE AND
 WPB UTILITIES DEPARTMENT
  
 4. IT APPEARS THAT SHEETS FROM THE MASTER SET OF PLANS
 WERE SUBMITTED INSTEAD OF SHEETS FROM THE FOUNDATION
 SET OF PLANS PLEASE REMOVE ANY PLAN SHEETS THAT DON'T
 PERTAIN TO THE FOUNDATION PERMIT. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  