2018-06-26 10:59:391) SHT. 1 OF 5 AND SHT. 3 OF 5 HAS A NOTE IN THE UPPER
 LEFT CORNER OF THE DRAWING THAT STATES THE POOL PIPING
 HAS BEEN DESIGNED ON THE MAXIMUM FLOW CAPACITY OF THE
 SWIMMING POOL PUMP. PLEASE CALARIFY HOW THIS CCOMPLIES
 WITH SEC. 4.4.9 OF APSP 7-2013.
 2) SHT. 3 OF 5 - SHOWS A VELOCITY CHART PER ANSI/APSP
 -7 SEC. 4.4.I COULD NOT FIND THIS CHART IN APSP-7 2013.
 CLARIFY.
 3) SUBMIT VERIFICATION / DOCUMENTATION TO SHOW
 COMPLIANCE WITH APSP 7-2014 SEC. 4.4.9 FOR MAXIMUM
 SYSTEM FLOW RATE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR