| Plan Review Notes For Permit 18060261 |
| Permit Number |
18060261 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-01 09:34:10 | PROVISO 18060261 | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE A BACKFLOW ON THE ICEMAKERS, WATER FILTERS | | | AND COFFEE MAKERS. PER FBC PL 608.3, 608.16.10 | | | 2. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTORS | | | APPROVAL. | | | 4. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH | | | EDITION 2017 | | | 5. TRAP PRIMER REQUIRED ON THE FLOOR DRAIN. PER FBC PL | | | 1002.4.1 | | | 6. THE NEW SINK DRAIN PIPING SHALL CONNECT TO BUILDING | | | BRANCH DRAIN DOWN STREAM OF THE EXISTING BATHROOM | | | GROUP. PER FBC PL 912.1 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|