| 2019-01-11 13:17:46 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PERMIT NEEDS TO BE ISSUED TO A LOW VOLTAGE OR |
| | ELECTRICAL CONTRACTOR (EC) GENERAL CONTRACTOR IS NOT |
| | ALLOWED TO PULL PERMIT FOR THIS TYPE OF WORK. NOT |
| | COMPLETED NEED TO CHANGE PERMIT TO BUILDING PERMIT WITH |
| | SUBS |
| | |
| | NEED CUT SHEETS FOR ALL CAMERAS, MOTION SENSORS, KEY |
| | PADS, CARD READERS, CABLES, ECT, ECT NOT DONE |
| | |
| | ALL EQUIPMENT SHALL BE LISTED AND USED INACCORDANCE |
| | WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS |
| | COMPLETED |
| | |
| | SHEET T2.10 NOT SURE WHAT PLAN IS SHOWING? COMPLETED |
| | |
| | SHEET T3.01 SEVERAL SYMBOLS NOT SHOWN IN LEGEND PP, NS, |
| | AMAG, PACS, PLC COMPLETED |
| | |
| | VALUE OF THE WORK SEEMS LOW PLEASE SUBMIT A SIGNED |
| | CONTRACT FOR THE WORK. NOT COMPLETED |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION |
| | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL |