| Notes |
| Date |
Text |
| 2018-07-06 10:58:45 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PERMIT NEEDS TO BE ISSUED TO A LOW VOLTAGE OR | | | ELECTRICAL CONTRACTOR (EC) GENERAL CONTRACTOR IS NOT | | | ALLOWED TO PULL PERMIT FOR THIS TYPE OF WORK. | | | | | | NEED CUT SHEETS FOR ALL CAMERAS, MOTION SENSORS, KEY | | | PADS, CARD READERS, CABLES, ECT, ECT | | | | | | ALL EQUIPMENT SHALL BE LISTED AND USED INACCORDANCE | | | WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS | | | | | | SHEET T2.10 NOT SURE WHAT PLAN IS SHOWING? | | | | | | SHEET T3.01 SEVERAL SYMBOLS NOT SHOWN IN LEGEND PP, NS, | | | AMAG, PACS, PLC | | | | | | VALUE OF THE WORK SEEMS LOW PLEASE SUBMIT A SIGNED | | | CONTRACT FOR THE WORK. | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING | | | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE | | | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION | | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL |
|