Plan Review Notes
Plan Review Notes For Permit 18060242
Permit Number 18060242
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-25 06:58:441) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN COVER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) INDICATE ON THE PUMP CURVE WHICH KEY CURVE IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 4) GENERAL NOTES PAGE - NOTE #8 - THE INFORMATION IN
 THIS NOTE IS FROM THE 2006 EDITION OF APSP 7. THE 2013
 EDITION IS IN EFFECT FOR THIS POOL. EITHER REVISE THE
 NOTE TO REFLECT THE CURRENT LANGUAGE IN APSP 7 SEC.
 4.4.9 OR DELETE THE NOTE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  