| Plan Review Notes For Permit 18060242 |
| Permit Number |
18060242 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-25 06:58:44 | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN | | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | | 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | | FITTING ASSEMBLY (DRAIN COVER). | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE MAIN DRAIN COVER. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 3) INDICATE ON THE PUMP CURVE WHICH KEY CURVE IS FOR | | | THE PUMP BEING INSTALLED ON THIS SYSTEM. WPB AMEND. TO | | | FBC SEC. 107.2.1. | | | 4) GENERAL NOTES PAGE - NOTE #8 - THE INFORMATION IN | | | THIS NOTE IS FROM THE 2006 EDITION OF APSP 7. THE 2013 | | | EDITION IS IN EFFECT FOR THIS POOL. EITHER REVISE THE | | | NOTE TO REFLECT THE CURRENT LANGUAGE IN APSP 7 SEC. | | | 4.4.9 OR DELETE THE NOTE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|