| Plan Review Notes For Permit 18060232 |
| Permit Number |
18060232 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-08-01 06:23:09 | 1) THE POOL PLANS SHOW TDH CALCULATIONS BASED ON THE | | | SIMPLIFIED TDH CALCULATION METHOD. THIS METHOD IS | | | ALLOWED IN THE 2006 VERSION OF APSP 7 BUT IS NO LONGER | | | ALLOWED IN THE 2013 EDITION OF APSP 7 WHICH HAS BEEN | | | ADOPTED BY THE 2017. | | | FBC. TOTAL DYNAMIC HEAD CALCULATIONS SHALL BE DONE IN | | | ACCORDANCE WITH 2013 APSP 7 SEC.4.4.9.1. | | | 2) TWO PUMP CURVES HAVE BEEN PROVIDED BUT THERE IS NO | | | INDICATION ON EITHER CURVE WHICH CURVE KEY IS SPECIFIC | | | TO THE TDH CALCULATIONS. THERE ARE DIFFERENT RPM'S ON | | | THE CURVES. CLARRIFY WHICH ONE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|