Text |
| 2018-07-14 10:09:14 | ***CORRECTIONS*** |
| | PERMIT # 18060221 |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 109] VALUE TOO LOW; PROJECT VALUE HAS BEEN |
| | ADJUSTED PER ICC TABLES: |
| | 448 SQ. FT. NEW UNDER AIR ADDITION X $130.95 |
| | 88 SQ. FT. PORCH X $21 |
| | |
| | 2. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO |
| | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. |
| | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION TO |
| | SUPPORT. UPDATE R-VALUES TO COMPLY WITH METHOD USED. |
| | |
| | 3. [FBC R302.11]ADD FIREBLOCKING TO DETAIL ON TYPICAL |
| | WALL SECTION. |
| | |
| | 4. [FBC R608.8]THE LINTEL SCHEDULE CALLS OUT TYPE "5" |
| | FOR LINTEL TO BE 5'-2" TO GO IN A 5'-4 R.O. |
| | YOU MAY NEED TO CHANGE TO TYPE "6" FOR LINTEL 5'-10" TO |
| | PROVIDE 4" OF BEARING AS REQUIRED FOR MASONRY. |
| | |
| | 5. IF USING SERIES 4000 ALUM SLIDING DOOR AS PROVIDE |
| | FULL N.O.A. NO.15-0818.07, AND PROVIDE PRODUCT APPROVAL |
| | FOR HURRICANE PROTECTION. INDICATE IF NOT USING AND WE |
| | WILL VOID SERIES 4000. |
| | |
| | 6. ARE EXISTING WINDOWS BEING REPLACED OR WERE THE |
| | SIZES WRITTEN IN FOR REFERENCE? IF THEY ARE BEING |
| | REPLACED PROVIDE PRESSURES AND PRODUCT APPRVAL FOR MULL |
| | BAR AND UPDATED VALUE. |
| | |
| | 7. [FBC R802.11]PROVIDE DESIGN PRESSURE FOR CLADDING |
| | AND COMPONANTS(ROOF AND WALLS). |
| | |
| | 8. [FBC 107, R301] PROVIDE AN INFILL DETAIL. |
| | |
| | 9. [FBC R FIGURE 301.2(7), ENHANCED NAIL NOTE, THE ROOF |
| | DIAGRAM DOES NOT APPEAR TO BE CONSISTENT WITH FIGURE R |
| | 301.2(7). IT APPEAR TO INCLUDE A RIDGE WITH ZONE 2; |
| | ISN'T THE NEW FLAT ROOF AREA LOW SLOPE (MONOSLOPE)? NO |
| | ZONE 3 SHOWN ON ONE SIDE. ISN'T A PARAPET ON ALL SIDES |
| | REQUIRED TO ELIMINATE ZONE 3? REVISE, OR PROVIDE |
| | RATIONALE, OR CONTACT ME TO DISCUSS. |
| | |
| | NOTE: |
| | WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | |
| | |