| 2018-06-29 12:19:00 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ALL MAINS SHOULD BE GROUPED PER NEC 230.72. RISER |
| | SHOWS AN 800 AMP SERVICE IN ONE LOCATION, A 600 AMP |
| | SERVICE IN ANOTHER LOCATION, AND THEN THE ADDITION OF |
| | THE 1200 AMP SERVICE IN A THIRD LOCATION. THIS WILL NOT |
| | BE ACCEPTABLE PER CODE. PREVIOUS APPROVAL OF PLAN FOR |
| | 1200 AMP SERVICE WILL NOT BE PERMITTED IN THIS |
| | LOCATION. PROVIDE CORRECTION SO THAT MAINS ARE GROUPED. |
| | NEC 230.72, 230.2 |
| | 2. PROVIDE JUSTIFICATION FOR ADDITIONAL 1200 AMP |
| | SERVICE. THE LOAD SHOWN ON THIS PANEL IS APPROXIMATELY |
| | 112 AMPS, ALTHOUGH THAT IS INCORRECT BECAUSE NO VALUE |
| | HAS BEEN ADDED FOR PANEL LPA. SEE COMMENT 3 FOR LOAD |
| | CALCULATION INFORMATION. NEC 230.2 |
| | 3. PROVIDE LOAD CALCULATION FOR EACH SERVICE INCLUDING |
| | EXISTING AND PROPOSED LOADS TO SHOW WHETHER THE |
| | EXISTING SERVICE IS ADEQUATE OR NOT FOR THE ADDITIONAL |
| | LOAD. ADDITIONALLY, THE LOAD CALCULATION SHOULD BE |
| | COMPLETED FOR ALL THREE PHASES. CURRENTLY, ONLY TWO OF |
| | THE PHASES ARE SHOWN. NEC 220; WPB FBC 107.2.1 |
| | 4. RISER DIAGRAM SHOWS A NEW PANEL LP FEED FROM |
| | EXISTING 600 AMP SERVICE. WHERE IS THIS PANEL LOCATED? |
| | THERE IS NO PANEL SCHEDULE FOR THIS? PROVIDE DETAILS. |
| | WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |