| 2018-06-16 19:34:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA. IT IS NOT CLEAR IF THIS IS A "SUBSTANTIAL |
| | IMPROVEMENT"; CUMULATIVE 5 YEAR IMPROVEMENTS EXCEED |
| | OVER 50% OF STRUCTURE VALUE. PROVIDE INFORMATION |
| | REGARDING THE PAST FIVE YEARS OF IMPROVEMENTS ON THIS |
| | STRUCTURE, VALUE OF THIS STRUCTURE, FBC B 1622. PLEASE |
| | FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE. |
| | ALTERNATIVELY, YOU COULD SHOW COMPLIANCE WITH THE |
| | REQUIREMENTS FOR NEW STRUCTURES - FINISHED FLOOR AND |
| | ALL EQUIPMENT SERVICING THE BUILDING TO BE AT OR ABOVE |
| | 14.2 NAVD88, OR PROVIDE DRY FLOODPROOFING TO 14.2 |
| | NAVD88, EXTERIOR EQUIPMENT ELEVATED TO MINIMUM 14.2 |
| | NAVD88. |
| | |
| | 2.FBC B TABLE 1604.5, RISK CATEGORY III IS REQUIRED FOR |
| | ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN |
| | 300, SHEET S2. SEE ALSO FBC EB 807. |
| | |
| | 3. 553.79(5), AS THIS IS AN ASSEMBLY OCCUPANCY WITH AN |
| | OCCUPANT LOAD OVER 500, THIS IS CLASSIFIED AS A |
| | THRESHOLD BUILDING. ALL PLANS PREPARED BY THE ARCHITECT |
| | AND ENGINEER ARE TO INCLUDE THE THRESHOLD STATEMENT |
| | REQUIRED BY FS553.79(7)(D). |
| | |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS CHAPTER 553 AND CHAPTER 633. |
| | |
| | 4. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| | OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO |
| | CONTRACTOR. |
| | |
| | 5. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| | PROPOSED INSPECTORS. |
| | |
| | 6. THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A). |
| | |
| | |
| | |