Plan Review Notes
Plan Review Notes For Permit 18060100
Permit Number 18060100
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-22 13:08:481. OK.
  
 2. OK.
  
 3. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 UPDATE PLANS TO SHOW INSULATION VALUES FROM THE ENERGY
 CALCULATIONS.
 3-2. NOT PROVIDED
  
 4. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL
 (ELP)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW
 FOR BUILDING FINAL.
 4-2. NOT PROVIDED
  
 5-17 OK.
  
 18. [FBC 107.2.1]N.O.A. FOR WINDOW ONLY COVERS WINDOWS
 UP TO 76" IN HEIGHT (TABLE 1&2). PLEASE PROVIDE N.O.A.
 FOR WINDOWS OVER 76" TALL.
 18-2. NO NEW PRODUCT APPROVAL PROVIDED.
  
 NEW COMMENT:
 19. VERIFY THAT THE FOOTER FOR THE SITE WALL WILL NEED
 TO BE WITHIN PROPERTY LINES.
 IF THE WALL IS TO EXTEND TO THE PROPERTY LINE PROVIDE
 DETAIL TO SHOW ECCENTRIC FOOTER TO KEEP THE FOOTER
 WITHIN PROPERTY LINES, WHILE ALLOWING WALL TO EXTEND TO
 PROPERTY LINE.
  
 20. ROOFING WAS APPROVED, BUT A NEW PRODUCT APPROVAL
 WAS SUBMITTED FOR SYSTEM OVER CONCRETE DECK.
 PLEASE VERIFY THAT THIS DOESN'T APPLY TO THIS PROJECT.
 I BELIEVE ALL ROOF DECK IS TO BE OVER PLYWOOD
 SHEATHING.
  
 18060108(DECK):
 1. OK.