Plan Review Notes
Plan Review Notes For Permit 18060100
Permit Number 18060100
Review Stop E
Sequence Number 1
Notes
Date Text
2018-06-27 10:48:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 3. RISER SHOWS THREE 3/0 CONDUCTORS TO INTERIOR PANEL.
 FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN EQUIPMENT
 GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 4. PROVIDE COMPLETE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS. SEE EXAMPLE IN FBC RESIDENTIAL. SOME ITEMS
 ARE NOT INCLUDED IN PANEL SCHEDULE, SUCH AS DISHWASHER.
 PROVIDE CORRECTIONS. NEC 220; FBC RE E3602.2
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 7. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8; FBC RE E3902.6
 8. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 9. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC
 210.63; FBC RE E3901.12
 10. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE: LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 11. LIGHTING IN OUTSIDE AREAS SHALL BE SUITABLE FOR
 DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(A); FBC
 RE E4003.9
 12. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  