2018-07-05 09:55:11****CORRECTIONS****
 W.P.B. PERMIT: 18060100(HOUSE) AND 18060108(DECK)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC R = FBC RESIDENTIAL
  
 18060100(HOUSE):
 IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES DUE, IF APPLICABLE, PROVIDED.
  
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
  
 561-233-5025 FOR MORE INFORMATION
  
 1. [FBC R107.2.5]PROVIDE ABSTRACTED SURVEY OF PROPERTY
 TO SHOW WHAT THE BUILD LINE ON SOUTH SIDE OF PROPERTY
 IS. IF THERE IS AN ULTIMATE RIGHT OF WAY THAN ADJUST
 BUILDING TO NOT ENCROACH THAT LINE.
  
 2. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN TO COMPLY
 WITH R401.3.
 SHOW LOWEST FLOOR ELEVATION (NAVD88) AND SHOW GRADE 4"
 BELOW FINISHED FLOOR SLAB FOR STARTING DRAINAGE SLOPES
 [FBC R404.1.6]. USE ELEVATION NUMBERS TO SHOW HOW
 DRAINAGE WORKS. AT WEST SIDE IF YOU CAN'T MAKE PITCH
 REQUIRMENTS, SHOW HOW WATER CAN BE HANDLED ON-SITE
 (PITCH FLAT ROOF TO EAST ONLY, GUTTERS AND UNDERGROUND
 DRAINS CAN BE UTILIZED).
  
 3. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 UPDATE PLANS TO SHOW INSULATION VALUES FROM THE ENERGY
 CALCULATIONS.
  
 4. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL
 (ELP)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW
 FOR BUILDING FINAL.
  
 5. [FBC R305]PROVIDE CEILING HEIGHTS FOR ALL ROOMS.
  
 6. [FBC R305]SHEET A.6 TYPICAL WALL SECTION SHOWS
 CEILING HGT. 10'(VERIFY). SHOULD THIS BE 12'(VERIFY)?
 ALSO, SHOW TYPICAL CONNECTION AT FLOOR AND CEILING FOR
 PARTITION WALLS.
  
  
 7. [FBC 107.3.5.3]PROVIDE DETAIL OF HOW OVERHANG WORKS
 ON THE NORTH & SOUTH ROOF, OR RESPOND THAT IT WILL BE
 SUBMITTED WITH TRUSS PACKAGE.
  
 8. [FBC R802.10]THE NOTE ON TOP OF DRAWING SHEET A.8
 STATES THAT TRUSSES ARE SPACED 16" C/C AND THE NOTES TO
 THE RIGHT STATE THEY ARE 24" C/C.
 PLEASE COORDINATE NOTES TO MATCH.
 ALSO, STATE CONNECTOR USED FOR EACH TRUSS AND SHOW X
 BRACING IF APPLICABLE.
  
 9. [FBC R608.8]IF LINTELS ARE BEING USED ABOVE WINDOWS
 AND DOORS, PROVIDE LINTEL SCHEDULE TO SHOW BEARING.
 PROVIDE LINTEL DOCUMENTATION FOR SAFE LOADING WITH
 LINTELS HIGHLIGHTED AND STAMPED APPROVED.
  
 10. [FBC 107.3.5.3]REMOVE NOTES THAT DON'T APPLY FROM
 SHEET A-9. DOES NOTE 18 APPLY TO BLOCK WALL?
  
 11. [FBC 107.3.5.3]TYPICAL COVER PATIO "B" SHOWS
 DRYWALL AND LOOKS THE SAME AS SECTION "A" OTHER NO
 INSULATION. SECTION "B" IS OUTSIDE AREA AND SHOULD SHOW
 MATERIALS THAT WOULD BE APPLIED FOR EXTERIOR TREATMENT,
 AND TRUSS ORIENTATION SHOULD MATCH. PLEASE
  
 12. [FBC R301.1]MARK THE PLAN WITH SECTION CUTS SO I
 CAN TELL WHERE YOU ARE DRAWINGS SECTIONS FROM.
  
 13. [FBC R904]WHAT MATERIALS ARE BEING USED FOR THE
 SOFFIT AND OVERHANG IN TYPICAL WALL SECTION. ADD NOTES
 TO SECTIONS AS APPLICABLE.
  
 14. [FBC R806]SUPPLY VENTING CALCULATIONS FOR THE ATTIC
 AND HOW THE AREA OF VENTING WILL BE ACHIEVED.
  
 15. [FBC R703.4]PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMNETS OF R703.4
  
 NOTICE OF ACCEPTANCE(N.O.A.):
  
 16. [FBC 107.2.1]PLASTPRO PRODUCT APPROVAL DOESN'T
 COMPLY WITH CURRENT CODE EDITION, AND IT DOESN'T COVER
 DOORS 10' HIGH. PLEASE RE-SUBMIT N.O.A. FOR ENTRY DOOR
 THAT MEETS REQUIRMENTS.
  
 17. [FBC 107.2.1]N.O.A. FOR GARAGE DOOR DOES NOT COVER
 DOORS WIDER THAN 16'. SHEET A.6 IS CALLING FOR AN 18'
 WIDE DOOR, SO PLEASE PROVIDE N.O.A. TO MEET CRITERIA.
  
 18. [FBC 107.2.1]N.O.A. FOR WINDOW ONLY COVERS WINDOWS
 UP TO 76" IN HEIGHT (TABLE 1&2). PLEASE PROVIDE N.O.A.
 FOR WINDOWS OVER 76" TALL.
  
 GENERAL NOTE FOR N.O.A'S:
 PLEASE HIGHLIGHT ON THE REVIEWED/APPROVED N.O.A'S THE
 APPLICABLE ITEM AND ATTACHMENT OPTIONS FOR THE PRODUCT
 BEING SPECIFIED.
  
  
 18060108(DECK):
 1. [FBC R107.3.5.3]PROVIDE DETAIL FOR BRICK PAVERS, OR
 INDICATE THAT SUBMITTAL WILL BE PROVIDED BY THE
 INSTALLER FOR PERMIT 18060108.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 PLEASE PROVIDE TWO IDENTICAL COPIES OF ALL ITEMS
 SUBMITTED AND A COMMENT RESPONSE SHEET.
  
  
  
  