| Plan Review Notes For Permit 18060073 |
| Permit Number |
18060073 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-25 05:26:07 | 1) LIST THE BTU LOAD OF THE EXISTING POOL HEATER AND | | | THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 | | | FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 | | | AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). 2ND | | | REQUEST. | | | 2) SHOW THE GAS METER ON THE GAS DRAWING AND THE | | | DISTANCE FROM THE GAS METER TO THE FARTHEST MP | | | REGULATOR.2ND REQUEST. | | | 3) SHOW THE TYPE & SIZE OF PIPE FROM THE EXISTING GAS | | | METER TO THE POOL HEATER. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|