| 2018-06-18 16:54:18 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE CHAPTER ONE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENT NOT ADDRESSED SATISFACTORILY. PREVIOUS |
| | COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY HAVE |
| | BEEN NOTED AS CORRECTED. ITEMS REMAINING HAVE FURTHER |
| | COMMENTS IN PARENTHESES. NEW COMMENTS FOLLOW THE |
| | PREVIOUS COMMENTS. |
| | |
| | 1. LOCATION OF CU-2 IS NOT CLEAR. IS IT LOCATED ON |
| | ROOF, OR IN BASEMENT NEXT TO OTHER UNITS AS REVISION |
| | INDICATES? PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 2. LOAD CALCULATION PROVIDED IS NOT SUFFICIENT. IT |
| | SEEMS STRANGE THAT THE LOAD WOULD GO FROM THE 798 AMPS |
| | STATED ON ORIGINAL PLAN TO 590 AMPS ON THIS REVISION |
| | AFTER THE INSPECTOR NOTED THAT THERE IS ONLY A 600 AMP |
| | SERVICE THERE. PROVIDE A DETAILED LOAD CALCULATION FOR |
| | ALL LOADS. NEC 220; WPB FBC 107.2.1 |
| | 3. BASED ON DISCUSSION WITH INSPECTOR, IS SEEMS THERE |
| | IS A 600 AMP DISCONNECT FOR THIS SERVICE NOT SHOWN ON |
| | PLAN. PROVIDE ACCURATE RISER DIAGRAM SHOWING THE |
| | SERVICE LOCATION AND INCLUDE DESCRIPTION OF THE NUMBER |
| | OF MAINS FOR THE SERVICE. NEC 230.2, 230.71, 230.72; |
| | WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |