Plan Review Notes
Plan Review Notes For Permit 18060039
Permit Number 18060039
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-12 09:44:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18060039
 MASTER #17010872
 6/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION
 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2014
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1: THE OUTDOOR AIR CALCULATIONS INDICATE A
 NEW DOA-1 PRODUCING 170 CFMS OF O/A, HOWEVER THE DOA
 APPARENTLY HAS BEEN REPLACED WITH AHU-2 WHICH IS
 PRODUCING 300 CFMS OF O/A ACCORDING TO THE AIR BALANCE
 SCHEDULE- PLEASE CORRECT.
  
 2) M0.1: THE REVISED AC SCHEDULE INDICATES THE NEW
 AHU-2/CU-2 IS A 9.3 TON SPLIT SYSTEM WITH AN AIR
 HANDLER THAT IS PRODUCING ONLY 1200 CFMS OF SUPPLY AIR.
 A 9.3 TON SYSTEM WOULD TYPICALLY PRODUCE APPROXIMATELY
 4000 CFMS OF AIR IF THE AIR HANDLER WAS MATCHED
 PROPERLY WITH THE CONDENSER. PLEASE CLARIFY THE
 DISCREPANCIES HERE AND THE NEED FOR SUCH A LARGE SYSTEM
 WHEN THE
 CALCULATIONS ARE CALLING FOR SUCH A SMALL AMOUNT OF O/A
 AIR.
  
 3) M0.1 & M1.1: THE AIR BALANCE SCHEDULE INDICATES THE
 KITCHEN HOOD EXHAUST AT -300 CFMS, HOWEVER THE PLAN
 INDICATES -1500 CFMS- PLEASE CLARIFY.
  
 4) M1.1 & E1.1: CLARIFY THE LOCATION OF THE NEW AHU-2
 CONDENSERS. THEY ARE SHOWN AT THE SIDEWALK GRATE
 LOCATION ON THE MECHANICAL PLANS WHICH INDICATES THAT
 THEY MAY BE GOING UNDER THE SIDEWALK BY THE EXISTING
 CU-1. THERE IS ALSO AN ENLARGED DETAIL OF THE ROOF
 STANDS WHICH HAS A CLOUDED NOTE INDICATING " NEW
 CONDENSING UNIT FOR DOA"., HOWEVER NO UNITS ARE SHOWN
 IN THE
 CLOUD. THE ELECTRICAL PLAN HAS A SECTION CUT SHOWING
 THE CONDNENSERS OF THE EXISTING ROOF STAND SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  