| 2018-06-12 09:44:57 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #18060039 |
| | MASTER #17010872 |
| | 6/12/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014 |
| | FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION |
| | 2014 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2014 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.1: THE OUTDOOR AIR CALCULATIONS INDICATE A |
| | NEW DOA-1 PRODUCING 170 CFMS OF O/A, HOWEVER THE DOA |
| | APPARENTLY HAS BEEN REPLACED WITH AHU-2 WHICH IS |
| | PRODUCING 300 CFMS OF O/A ACCORDING TO THE AIR BALANCE |
| | SCHEDULE- PLEASE CORRECT. |
| | |
| | 2) M0.1: THE REVISED AC SCHEDULE INDICATES THE NEW |
| | AHU-2/CU-2 IS A 9.3 TON SPLIT SYSTEM WITH AN AIR |
| | HANDLER THAT IS PRODUCING ONLY 1200 CFMS OF SUPPLY AIR. |
| | A 9.3 TON SYSTEM WOULD TYPICALLY PRODUCE APPROXIMATELY |
| | 4000 CFMS OF AIR IF THE AIR HANDLER WAS MATCHED |
| | PROPERLY WITH THE CONDENSER. PLEASE CLARIFY THE |
| | DISCREPANCIES HERE AND THE NEED FOR SUCH A LARGE SYSTEM |
| | WHEN THE |
| | CALCULATIONS ARE CALLING FOR SUCH A SMALL AMOUNT OF O/A |
| | AIR. |
| | |
| | 3) M0.1 & M1.1: THE AIR BALANCE SCHEDULE INDICATES THE |
| | KITCHEN HOOD EXHAUST AT -300 CFMS, HOWEVER THE PLAN |
| | INDICATES -1500 CFMS- PLEASE CLARIFY. |
| | |
| | 4) M1.1 & E1.1: CLARIFY THE LOCATION OF THE NEW AHU-2 |
| | CONDENSERS. THEY ARE SHOWN AT THE SIDEWALK GRATE |
| | LOCATION ON THE MECHANICAL PLANS WHICH INDICATES THAT |
| | THEY MAY BE GOING UNDER THE SIDEWALK BY THE EXISTING |
| | CU-1. THERE IS ALSO AN ENLARGED DETAIL OF THE ROOF |
| | STANDS WHICH HAS A CLOUDED NOTE INDICATING " NEW |
| | CONDENSING UNIT FOR DOA"., HOWEVER NO UNITS ARE SHOWN |
| | IN THE |
| | CLOUD. THE ELECTRICAL PLAN HAS A SECTION CUT SHOWING |
| | THE CONDNENSERS OF THE EXISTING ROOF STAND SYSTEM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |