| Plan Review Notes For Permit 18051500 |
| Permit Number |
18051500 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-06-04 10:32:02 | 1) THERE IS A REFERENCE ON THE GAS PLAN TO SIZING TABLE | | | 402.4 (28). THIS TABLE IS FOR SIZING LP GAS, NOT | | | NATURAL GAS. SUBMIT THE CORRECT TABLE. | | | 2) SHOW THE DISTANCE OF THE TANKLESS WATER HEATERS IN | | | RELATION TO WINDOWS, DOORS AND OTHER BUILDING OPENINGS. | | | THE TANKLESS WATER HEATER SHALL BE LOCATED A MINIMUM OF | | | 4 FEET FROM ANY OPERABLE WINDOW OR DOOR. | | | 3) THE GAS POOL HEATER SHALL HAVE A MINIMUM THERMAL | | | EFFICIENCY OF 82% PER 2017 FBC-ENERGY | | | SEC.R403.10.4.SUBMIT DOCUMENTATION THAT THE POOL HEATER | | | MEETS THIS CRITERIA. | | | NOTE: A HOOD WILL BE REQUIRED OVER THE GRILL. 2017 | | | FBCR-SEC. G2406.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | | | | |
|