Plan Review Notes
Plan Review Notes For Permit 18051500
Permit Number 18051500
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-04 10:32:021) THERE IS A REFERENCE ON THE GAS PLAN TO SIZING TABLE
 402.4 (28). THIS TABLE IS FOR SIZING LP GAS, NOT
 NATURAL GAS. SUBMIT THE CORRECT TABLE.
 2) SHOW THE DISTANCE OF THE TANKLESS WATER HEATERS IN
 RELATION TO WINDOWS, DOORS AND OTHER BUILDING OPENINGS.
 THE TANKLESS WATER HEATER SHALL BE LOCATED A MINIMUM OF
 4 FEET FROM ANY OPERABLE WINDOW OR DOOR.
 3) THE GAS POOL HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82% PER 2017 FBC-ENERGY
 SEC.R403.10.4.SUBMIT DOCUMENTATION THAT THE POOL HEATER
 MEETS THIS CRITERIA.
 NOTE: A HOOD WILL BE REQUIRED OVER THE GRILL. 2017
 FBCR-SEC. G2406.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  
  