| 2018-06-21 06:46:31 | 1) THE EXISTING GAS PLANS ON FILE IN THE CITY HAVE THE |
| | FOLLOWING INFORMATION FOR THE EXISTING BTU LOAD: |
| | A) WATER HEATER - 55,000 BTU'S |
| | B) GAS DRYER - 35,000 BTU'S |
| | C) BBQ - 40,000 BTU'S |
| | D) POOL HEATER - 400,000 BTU'S |
| | THESE VALUES SHALL BE USED FOR THE EXISTING BTU LOAD ON |
| | YOUR PLANS. |
| | 2) THE TOTAL BTU LOAD WILL BE 850,000 BTU'S. THE GAS |
| | METER SHALL BE CHECKED TO ENSURE THAT IT WILL HANDLE |
| | THE TOTAL BTU LOAD OF THE SYSTEM. CONTACT THE GAS |
| | PURVEYOR FOR FURTHER DIRECTION. THIS WILL BE CHECKED BY |
| | THE FIELD INSPECTOR AT FINAL INSPECTION. |
| | 3) SUBMIT TWO COPIES OF THE INSTALLATION INTRUCTIONS |
| | FOR THE REGULATOR.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING |
| | SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER 2017 |
| | FBC-GAS SEC.410.1. THE REGULATOR SPECS DO NOT SHOW |
| | THIS. |
| | 5) INDICATE ON THE REGULATOR SPECS THE MODEL BEING |
| | INSTALLED.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| | CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| | BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL |
| | GAS SEC. 411.1.3.2. |
| | 7) THE EXISTING GAS PLANS ON FILE IN THE CITY SSHOW AN |
| | 1 1/2 INCH GALVANIZED LINE FROM THE METER OUTLET AND A |
| | 1 INCH GALVANIZED LINE TO THE INTERIOR AND YOUR PLAN |
| | SHOWS A 3/4 INCH LINE AT BOTH POINTS. CLARIFY. |
| | 8) INDICATE ON THE PLANS THE SIZING TABLE FOR THE LOW |
| | PRESSURE SIDE FOR THE GENERATOR. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |