| Plan Review Notes For Permit 18051467 |
| Permit Number |
18051467 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-16 10:32:10 | 2ND REVIEW: FBC FIFTH EDITION (2014) REFERENCE PRIMARY | | | PERMIT 16040430 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING (COMMENTS FROM 1ST REVIEW WERE NOT | | | ADDRESSED) | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF GENERATOR PAD PLANS. PROVIDE PAD | | | DIMENSIONS AND LOCATION. SPECIFY THE SIZE, TYPE AND | | | QUANITY OF ANCHORS FOR THE GENERATOR TO SLAB | | | CONNECTIONS. FBC 107.2.1 | | | | | | 2) THE PROJECT IS LOCATED IN AN A5 SPECIAL FLOOD HAZARD | | | ZONE AN ELEVATION CERTIFICATE WILL BE REQUIRED TO BE | | | SUBMITTED AND APPROVED BEFORE FINAL INSPECTION. THE | | | MINIMUM ELEVATION FOR THIS PROJECT IS 7.5' NGVD BASED | | | ON THE FIRMS IN EFFECT AT THE TIME THE SINGLE FAMILY | | | HOME THIS GENERATOR WILL SERVICE WAS PERMITTED. | | | |
|