Plan Review Notes
Plan Review Notes For Permit 18051464
Permit Number 18051464
Review Stop E
Sequence Number 2
Notes
Date Text
2018-10-08 07:20:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PAGE E3.0 OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH
 ASHRSE 90.1 SECTION 8.4.2 PROVIDE RECEPTACLE CONTROL
 REQUIRED BY ASHREA 90.1: 8.4.2. FBC CE 405.7.1
 (RESPONSE LETTER STATES THIS IS NOT REQUIRED PER THE
 FBC ENERGY, WHICH IS INCORRECT. SEE FBC EC 405.6.1.
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1)
 3. E3.1 NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON
 ROOF. (SHEET M2.0 DOES NOT STATE IF THIS "CONVENIENCE
 OUTLET" IS GFCI PROTECTED PER CODE. PROVIDE
 CLARIFICATION AND/OR CORRECTION. NEC 210.8, 210.63)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
  
 NEW COMMENT:
  
 9. DIGITAL SIGNATURES ARE CORRUPTED. SEE COMMENTS UNDER
 SIGNATURE STOP. FS 471/481; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  