Plan Review Notes
Plan Review Notes For Permit 18051464
Permit Number 18051464
Review Stop B
Sequence Number 2
Notes
Date Text
2018-09-28 08:24:36****CORRECTIONS****
 W.P.B. PERMIT: 18051464
 REVIEWED: AUGUST 15, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1-8. OK
  
 8. THE GEOTECHNICAL REPORT SITE PREPARATION MENTIONS
 THE REMOVAL OF TANKS. DOES THE REPORT STATE HOW TO
 HANDLE THE INFILL FROM SUCH A LARGE EXCAVATION? THIS
 OCCURS UNDER THE BUILDING SITE AND THE REPORT SHOULD
 ADDRESS HOW TO ACHIEVE THE 3000PSF REQUIRED.
  
 8-2. CONTRACTOR STATED THAT THEY WOULD PROVIDE A
 GEOTECHNICAL REPORT PRIOR FILLING IN HOLE FROM THE FUEL
 TANK REMOVAL.
 SUPPLY REPORT, OR INDICATE THAT YOU WOULD LIKE IT TO BE
 A PROVISO.
  
  
 9 SEPARATE PERMITS WILL BE REQUIRED FOR SEPARATE
 STRUCTURES.
 DRIVE THRU CANOPY, DUMPSTER ENCLOSURE, FENCE(IF
 APPLICABLE), LANDSCAPING, SITE LIGHTING(PROVIDE POLE
 WIND CALCS) AND ENGINEERING TO PERMIT CIVIL WORK.
 9-2. PROVIDE PERMIT NUMBER FOR THE DRIVE THRU CANOPY
 AND DUMPSTER ENCLOSURE.
  
 10-14. OK
  
 15. [FBC 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED. DEFERRED
 SUBMITTALS TO BE REVIEWED PRIOR TO INSTALLATION.
  
 15-2. PROVISO:
 TRUSS SHOP DRAWINGS TO BE PROVIDED TO INSPECTOR PRIOR
 TO INSTALLATION.
  
 KAWNEER DOORS DON?T PROVIDE FOR WATER INFILTRATION.
 PLEASE PROVIDE REQUIREMENTS SET FORTH WATER
 INFILTRATION.
 [FBC 1710.5.1.1]EXTERIOR WINDOWS AND DOORS (HABITAL
 SPACES). (EXCEPTION) 2. DOOR ASSEMBLIES INSTALLED WHERE
 THE OVERHANG (OH) RATIO IS EQUAL TO OR MORE THAN 1 NEED
 NOT BE TESTED FOR WATER INFILTRATION. THE OVERHANG
 RATIO SHALL BE CALCULATED BY THE FOLLOWING EQUATION:
 OH RATIO = OH LENGTH/OH HEIGHT
 WHERE:
 OH LENGTH = THE HORIZONTAL MEASURE OF HOW FAR AN
 OVERHANG OVER A DOOR PROJECTS OUT FROM DOOR SURFACE.
 OH HEIGHT = THE VERTICAL MEASURE OF THE DISTANCE FROM
 THE DOOR SILL TO THE BOTTOM OF THE OVERHANG OVER A
 DOOR.
  
 RESPONSE: THE KAWNEER?S 350 IR SIDE-HINGED DOORS NOA #
 15-0622.11 COMPLIES WITH FBC 1709.5.1 EXCEPTION: ?DOOR
 ASSEMBLIES INSTALLED IN NONHABITABLE AREAS WHERE THE
 DOOR ASSEMBLY AND AREA ARE DESIGNED TO ACCEPT WATER
 INFILTRATION NEED NOT BE TESTED FOR WATER
 INFILTRATION.? ACCORDING THE MANUFACUTURER THE KAWNEER
 DOOR IS DESIGNED TO ACCEPT WATER AND DETER IT BY THE
 BULB GASKETS ALONG THE PERIMETER FRAMING WHERE IT MEETS
 THE DOOR.
  
 15-2. I?M LOOKING AT NOA 15-0622.11 NOTE ON SHEET 1 OF
 9.
 IT STATES THAT THESE DOORS ARE NOT APPROVED FOR USE
 WHERE WATER INFILTRATION RESISTANCE IS REQUIRED.
 PLEASE PROVIDE REPONSE THAT DOESN?T INCLUDE THE DOORS
 MEETING REQUIREMENTS FOR WATER INFITRATION, BUT RATHER
 STATE HOW YOU ARE MEETING THE EXCEPTION REQUIRING THE
 AREA TO ACCEPT WATER INFILTRATION IN A NONHABITABLE
 AREA.
  
  
 16. OK.
  
 NEW COMMENT:
 17. PLEASE REPLACE NOA 16-0510.28 FOR ROOF VENTS WITH
 NOA 15-0922.06 FOR ROOF VENTS AS STATED IN COMMENT
 RESPONSE SHEET DATED SEPTEMBER 18, 2018.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  