| 2018-08-16 08:57:30 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18051464 | | | REVIEWED: AUGUST 15, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. ON PRODUCT APPROVAL TPO ROOFING NOA 17-0727.01 | | | INDICATE WHICH SYSTEM IS BEING USED TO ACHIEVE DESIGN | | | LOAD, OR INDICATE TO DEFER ROOFING SUBMITTAL. | | | | | | 2. PROVIDE PRODUCT APPROVAL AND ATTACHMENT FOR ROOF | | | INSULATION, OR INDICATE THAT IT WILL BE DEFERRED. | | | DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO | | | INSTALLATION. | | | | | | 3. ON PRODUCT APPROVAL FOR ROOF VENTS. VERIFY THE | | | APPROVED APPLICATION WORKS FOR SPANISH TILE. I SEE | | | APPROVAL FOR SHINGLE AND STANDING SEAM. | | | | | | 4. SHOW ROOF FIRE CLASSIFICATION ON ROOFING PLAN | | | |
|