Plan Review Notes
Plan Review Notes For Permit 18051464
Permit Number 18051464
Review Stop M
Sequence Number 1
Notes
Date Text
2018-07-31 16:54:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18051464
 7/31/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEMS- SECTION C403.2.1 FBC-17 EC INCLUDING THE
 RTU'S AND FAN COIL SYSTEMS.
  
 2) THE COMCHECK ENERGY COMPLIANCE CERTIFICATE, AND THE
 MECHANICAL PLANS ARE NOT ELECTRONICALLY SIGNED AND
 SEALED AS REQUIRED BY SECTION 61G15-23.005 FAC.
  
 3) SHEET M1.1: PROVIDE WIND LOAD ENGINEERING FOR TIE
 DOWN OF THE RTU'S - SECTION 301.15. INCLUDE THE DESIGN
 CRITERIA IN ACCORDANCE WITH SECTION 1609 FBC B, AND
 COMPLETE DETAILS FOR ANCHORING THE CURBS TO THE
 STRUCTURE, AND MOUNTING THE UNITS TO THE CURBS.
  
 4) M1.1: SHOW THE CONDENSATE PIPING RUNS AND DISCARGE
 LOCATIONS. PLEASE INDICATE THE SIZE OF THE PIPING, AND
 SHOW HOW THE PIPING WILL BE SUPPORTED ABOVE THE ROOF
 AND THE TYPE AND SPACING OF THE PIPE SUPPORTS.
  
 5) SUBMIT THE FL. PRODUCT APPROVAL # 16921.1-R3 FOR THE
 CONDENSER ROOF STAND.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  