| 2018-07-06 12:57:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 2.1 - THIS PLAN SHEET IS INDICATED AS LIFE |
| | SAFETY PLAN AND DETAILS. |
| | |
| | BE ADVISED, THIS PLAN INDICATED ACCESSIBILITY DETAILS |
| | WITH NO LIFE SAFETY. |
| | |
| | PLEASE REVIEW AND PROVIDE AN ACCURATE LIFE SAFETY PLAN |
| | AND DETAILS. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 2.1 - THERE ARE INDICATIONS OF THE HARDWARE |
| | ON THE MAIN ENTRY DOORS OF MORTISE CYLINDERS. |
| | |
| | PER NFPA 101, CHAPTER 38, NEW BUSINESS OCCUPNACIES AND |
| | CHAPTER 7, MEANS OF EGRESS: |
| | |
| | 38.2.2 MEANS OF EGRESS COMPONENTS. |
| | 38.2.2.1 GENERAL. MEANS OF EGRESS COMPONENTS SHALL BE |
| | LIMITED |
| | TO THE TYPES DESCRIBED IN 38.2.2.2 THROUGH 38.2.2.12. |
| | 38.2.2.2 DOORS. |
| | 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | AND |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | |
| | PLEASE REVIEW, CORRECT OR PROVIDE SPECIFIC DETAILS OF |
| | COMPLIANCE |
| | |
| | |
| | |
| | 3) SHEET A 2.1 - THERE ARE INDICATIONS OF A PANIC BAR |
| | ON THE ENTRY DOORS. |
| | |
| | PER NFPA 101, CHAPTER 7 |
| | |
| | 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE. |
| | 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE |
| | EQUIPPED WITH |
| | PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET |
| | ALL OF THE |
| | FOLLOWING CRITERIA: |
| | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE |
| | ACTUATING |
| | PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF |
| | OF THE |
| | WIDTH OF THE DOOR LEAF. |
| | (2) IT SHALL BE MOUNTED AS FOLLOWS: |
| | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. |
| | (865 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 |
| | IN. (760 MM), |
| | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. |
| | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE |
| | NOT TO EXCEED |
| | 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND |
| | LATCHES. |
| | |
| | AND |
| | |
| | 7.2.1.7.3 REQUIRED PANIC HARDWARE AND FIRE EXIT |
| | HARDWARE, IN OTHER |
| | THAN DETENTION AND CORRECTIONAL OCCUPANCIES AS |
| | OTHERWISE PROVIDED |
| | IN CHAPTERS 22 AND 23, SHALL NOT BE EQUIPPED WITH ANY |
| | LOCKING |
| | DEVICE, SET SCREW, OR OTHER ARRANGEMENT THAT PREVENTS |
| | THE RELEASE |
| | OF THE LATCH WHEN PRESSURE IS APPLIED TO THE RELEASING |
| | DEVICE. |
| | |
| | THOUGH PANIC HARDWARE IS NOT REQUIRED FOR THIS |
| | OCCUPANCY, IF INSTALLED, IT MUST BE INSTALLED PER THE |
| | APPLICABLE CODE. |
| | |
| | PLEASE REVIEW AND REMOVE THE PANIC BAR OR EXPLAIN WITH |
| | SPECIFC DETAILS AND FIRE CODE REFERENCES. |
| | |
| | |
| | |
| | 4) SHEET A 2.1 - THERE ARE INDICATIONS OF ELECTROINC |
| | LOCKS OR STRIKES WITHIN THE DOOR SCHEDULE. |
| | |
| | NO DOOR SHALL BE LOCKED AGAINST EGRESS. |
| | |
| | ALL ACCESS AND/OR EGRESS CONTROL SHALL BE COMPLY WITH |
| | THE APPLICABLE REQUIREMENTS FO NFPA 101, CHAPTER 7, |
| | MEANS OF EGRESS AND BE SUBMITTED UNDER A SEPARATE SHOP |
| | DRAWING PERMIT. |
| | |
| | PLEASE REVIEW, CORRECT AND PROVIDE AN APPLICABLE NOTE |
| | OF ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |