| Notes |
| Date |
Text |
| 2018-08-07 14:35:21 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | E0.1 | | | | | | TAP OFF MAIN TO POWER METER AND TO WAC SYSTEM HOW IS | | | THIS GOING TO BE CONNECTED? | | | | | | BUILDING MANAGEMENT SYSTEM TO COMPLY WITH ARTICLE 750 | | | OF THE NEC | | | | | | PAGE E3.0 | | | | | | OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH ASHRSE 90.1 | | | SECTION 8.4.2 | | | PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC CE 405.7.1 | | | | | | E3.1 | | | | | | NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON ROOF. | | | | | | E7.0 | | | | | | LOAD CACLUATION NOT CALCULATED PER 220 OF THE NEC | | | THE ONE SHOWN ON E7.0 SHOWS LIGHTING LOAD OF 2.9KW? | | | | | | FAULT CURRENT CALCULATION REQUIRED FOR ALL SERVICE | | | EQUIPMENT AND DOWN STREAM PANELS | | | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE | | | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT | | | CURRENT IS FOR THE SERVICE TO CONFIRM | | | THE STATED AIC RATING OF THE SERVICE EQUIPMENT AND | | | DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10 | | | | | | PROVIDE ENERGY CALCULATION FOR THE INTERIOR LIGHTING. | | | | | | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING | | | COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5 | | | |
|