2018-08-07 14:35:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 E0.1
  
 TAP OFF MAIN TO POWER METER AND TO WAC SYSTEM HOW IS
 THIS GOING TO BE CONNECTED?
  
 BUILDING MANAGEMENT SYSTEM TO COMPLY WITH ARTICLE 750
 OF THE NEC
  
 PAGE E3.0
  
 OUTLETS IN OPEN OFFICE AREA TO COMPLY WITH ASHRSE 90.1
 SECTION 8.4.2
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
  
 E3.1
  
 NO OUTLETS ON ROOF TO SERVICE EQUIPMENT ON ROOF.
  
 E7.0
  
 LOAD CACLUATION NOT CALCULATED PER 220 OF THE NEC
 THE ONE SHOWN ON E7.0 SHOWS LIGHTING LOAD OF 2.9KW?
  
 FAULT CURRENT CALCULATION REQUIRED FOR ALL SERVICE
 EQUIPMENT AND DOWN STREAM PANELS
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM
 THE STATED AIC RATING OF THE SERVICE EQUIPMENT AND
 DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10
  
 PROVIDE ENERGY CALCULATION FOR THE INTERIOR LIGHTING.
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5
  